Rosemount 1151 Transmitter

Original
price: Negotiable
minimum:
Total supply:
Delivery term: The date of payment from buyers deliver within days
seat: Beijing
Validity to: Long-term effective
Last update: 2017-10-25 20:52
Browse the number: 441
inquiry
Company Profile
 
 
Product details
    Rosemount 1151 Transmitter

 

 Proven field performance and reliability :


• Commitment to continuous improvement
• Reference accuracy of 0.075%
• Two-year stability of 0.1%
• Rangeability of 50:1

 

 Specifications:

 

Static Pressure Limits


Transmitters operate within specifications between the following
limits:
Rosemount 1151DP
0.5 psia to 2,000 psig (3.45 kPa to 13790 kPa).


Rosemount 1151HP
0.5 psia to 4,500 psig (3.45 kPa to 31027 kPa).


Rosemount 1151AP
0 psia to the URL

.
Rosemount 1151GP
0.5 psia (3.45 kPa) to the URL.


Rosemount 1151LT
Limit is 0.5 psia (3.45 kPa) to the flange rating or sensor rating,
whichever is lower.

Overpressure Limits
Transmitters withstand the following limits without damage:
Rosemount 1151DP
0 psia to 2,000 psig (0 to 13790 kPa).


Rosemount 1151HP
0 psia to 4,500 psig (0 to 31027 kPa).

Rosemount 1151AP
0 psia to 2,000 psia (0 to 13790 kPa).


Rosemount 1151GP
Ranges 3–8: 0 psia to 2,000 psig (0 to 13790 kPa).
Range 9: 0 psia to 4,500 psig (31027 kPa).
Range 0: 0 psia to 7,500 psig (51710 kPa).


Rosemount 1151LT
Limit is 0 psia to theflange rating or sensor rating, whichever
is lower

 

 


PERFORMANCE SPECIFICATIONS
(Zero-based calibrated ranges, reference conditions, silicone oil fill, 316 SST isolating diaphragms for HART 4-20 mA protocol.)


Accuracy

 